Influence of Phase-Shifting Transformers (PSTs) on the Distance Protection of Transmission Lines and Improve the Performance of Distance Relay

Message:
Article Type:
Research/Original Article (دارای رتبه معتبر)
Abstract:
Background and Objectives

With the ever-increasing growth of electric loads, the need for generating electric power grows correspondingly. By considering the limitations of power generation, utilizing novel technologies has gained persistent momentum, one of which is deploying Phase-Shifting Transformers (PSTs). Among the more important available relays for the transmission lines are Distance Relays. To this end, Distance Relays measure the voltage and current of the transmission line in its final installation location. On the other hand, the existence of Phase-Shifting Transformers on transmission lines alters the voltage and current signals at the relay location. This issue causes the impedance calculated by the relay to differ from its actual value at the fault location. As a result, the relay detects the fault location falsely, or in some cases does not recognize it at all.

Methods

The effect of phase shifting transformer on the relay performance of the distances has been investigated in this study. Furthermore, the digital distance relays are modeled in a software environment and its validity is investigated through analytical relationships. Next, the efficacy of the transformer on distance protection is analytically studied. Finally, a new method has been proposed to improve distance relay performance.

Results

Results from analysis and modelling shows that the effect of phase shifting transformers in relay-computed impedance has two faces, the first of which is related to the internal impedance of the transformer, while the other regards the serial voltage of the transformer. The latter face is much more influential than the former one.

Conclusion

This fact renders the mere inner Impedance of phase-shifting transformer insufficient for using it to eliminate its effect. To this end, a method has been developed in which the voltages of both ends of the phase shifting transformer are measured by the PMUs and then sent to the facility for protecting power system after synchronization. There, this voltage is reduced from the voltage calculated by the relay, which renders the effect of the phase shifting transformer in the impedance calculated by the relay completely eliminated. 

Language:
English
Published:
Journal of Electrical and Computer Engineering Innovations, Volume:9 Issue: 2, Summer-Autumn 2021
Pages:
173 to 184
https://magiran.com/p2285242  
دانلود و مطالعه متن این مقاله با یکی از روشهای زیر امکان پذیر است:
اشتراک شخصی
با عضویت و پرداخت آنلاین حق اشتراک یک‌ساله به مبلغ 1,390,000ريال می‌توانید 70 عنوان مطلب دانلود کنید!
اشتراک سازمانی
به کتابخانه دانشگاه یا محل کار خود پیشنهاد کنید تا اشتراک سازمانی این پایگاه را برای دسترسی نامحدود همه کاربران به متن مطالب تهیه نمایند!
توجه!
  • حق عضویت دریافتی صرف حمایت از نشریات عضو و نگهداری، تکمیل و توسعه مگیران می‌شود.
  • پرداخت حق اشتراک و دانلود مقالات اجازه بازنشر آن در سایر رسانه‌های چاپی و دیجیتال را به کاربر نمی‌دهد.
In order to view content subscription is required

Personal subscription
Subscribe magiran.com for 70 € euros via PayPal and download 70 articles during a year.
Organization subscription
Please contact us to subscribe your university or library for unlimited access!