Optimal Coordination of Overcurrent Relays in Distribution Systems Connected to the Microgrid Using Active Superconducting Fault Current Limiter
Active superconducting fault current limiter (ASFCL) is a new type of FCLs which can limit the fault current at different levels. It also has a particular ability to compensate for voltage series in the electrical power systems. In this paper, an optimal coordination method is proposed to calculate both optimal setting parameters of overcurrent relays (OCRs) and limiting the impedance of ASFCL. The optimal parameters of OCRs are obtained using the maximum pickup current and minimum trip time method. In the next step, by applying a new DG unit to the microgrid, the optimal limiting impedance of ASFCL is obtained so that all OCRs could be coordinated without changing the relay setting parameters. Using MATLAB software, a typical distribution system connected to a microgrid with ASFCL is simulated and the simulation results are evaluated in terms of the fault current limitation and OCRs coordination. Simulation results confirm the appropriate performance of the proposed ASFCL for the above-mentioned purposes.
- حق عضویت دریافتی صرف حمایت از نشریات عضو و نگهداری، تکمیل و توسعه مگیران میشود.
- پرداخت حق اشتراک و دانلود مقالات اجازه بازنشر آن در سایر رسانههای چاپی و دیجیتال را به کاربر نمیدهد.